ActronAir CRE-100AS / URC-100AS 10kW Cassette Split System - CRE-100AS / URC-100AS
ActronAir CRE-100AS / URC-100AS 10kW Cassette Split System - CRE-100AS / URC-100AS
Couldn't load pickup availability
ActronAir CRE-100AS / URC-100AS 10kW Cassette Split System - CRE-100AS / URC-100AS
ActronAir CRE-100AS / URC-100AS 10kW Cassette Split System - CRE-100AS / URC-100AS
The ActronAir CRE-100AS / URC-100AS 10kW Cassette Split System offers superior climate control with advanced technology and a sleek design. Equipped with a powerful 10kW cooling and 10.7kW heating capacity, this system efficiently maintains comfort in diverse environments. The unit features an inverter twin-rotary compressor, R410A refrigerant, and a premium wired controller for precise settings. Ideal for both residential and commercial spaces, it seamlessly integrates into any setting, ensuring consistent performance with minimal energy consumption.
Specifications
| Technical Information | ||
|---|---|---|
| OUTDOOR MODEL | URC-100AS | |
| INDOOR MODEL | CRE-100AS | |
| Nett (Rated) Capacity (kW) (AS/NZS3823.1.1) | Cooling (min max) | 10.50 (4.20 - 12.60) |
| Heating (min max) | 10.70 (4.32 - 12.95) | |
| Input Power (kW) (AS/NZS3823.1.1) | Cooling Rated | 3.11 |
| Heating Rated | 2.88 | |
| EER Rated (AS/NZS3823.1.1) / COP Rated (AS/NZS3823.1.1) | Cooling | 3.38 |
| Heating | 3.72 | |
| Star Rating (AS/NZS3823.1.1) | Cooling | 2.0 |
| Heating | 2.5 | |
| Power Supply (V / Ph / Hz) | Outdoor | 220 240 V / 1Ph+N / 50Hz |
| Rated Load Amps (AS/NZS3823.1.1) | Cooling | 13.7 |
| Heating | 12.7 | |
| Full Load Amps (AS/NZS3823.1.1) | 21.5 | |
| Circuit Breaker Amps | 25.0 | |
| Suggested Minimum Mains Cable Size | 4.0mm² | |
| Suggested Minimum Indoor to Outdoor Power Cable Size & Type | 1.0mm² 2 Core + Earth | |
| IP Rating | Outdoor | IP24 |
| Indoor | IP20 | |
| Moisture Removal (L/hr) | 1.7 | |
| Compressor Type | Inverter Twin-Rotary | |
| Refrigerant | R410A | |
| Airflow Range Indoor (l/s) | High | 444 |
| Medium | 408 | |
| Low | 361 | |
| Outdoor Dimensions (mm) | Depth | 410 |
| Height | 810 | |
| Width | 946 | |
| Indoor Dimensions (mm) | Depth | 840 |
| Height | 287 | |
| Width | 840 | |
| Indoor Panel Dimensions (mm) | Depth | 950 |
| Height | 55 | |
| Width | 950 | |
| Nominal Weight (kgs) | Outdoor | 69 |
| Indoor | 36 | |
| Indoor Sound Pressure Level (dBA) (Low / Med / High) | 44 / 48 / 51 | |
| Outdoor Sound Pressure Level (dBA) 1m | 62 | |
| Outdoor Sound Power Level (dBA) | 70 | |
| Outdoor Operating Range (C) | Cooling | -15C to 50C |
| Heating | -25C to 30C | |
| MEPS Compliant | Yes | |
| Demand Response Capability (AS4755.3) | Capable | |
What our Experts Think
- High-capacity cassette comfort system: The ActronAir CRE-100AS / URC-100AS is a 10–10.5 kW reverse-cycle cassette split system, designed for large rooms, offices, and open-plan spaces, delivering strong all-season heating and cooling performance.
- Powerful whole-space coverage: With around 10.5 kW cooling and 10.7 kW heating capacity, it’s built to maintain stable comfort in medium-to-large zones, even in demanding climates.
- 360° air distribution advantage: The 4-way cassette airflow design spreads conditioned air evenly across the room, reducing hot/cold spots and improving overall comfort consistency.
- Efficient inverter operation: Uses a twin-rotary inverter compressor, adjusting output dynamically to match demand, helping improve efficiency and reduce energy waste during partial loads.
- Strong operating range: Performs reliably in extreme conditions, operating from -25°C heating to 50°C cooling, making it suitable for demanding environments.
- Quiet, discreet indoor design: The cassette format is ceiling-mounted and low-profile, keeping interiors clean and uncluttered while maintaining effective airflow distribution.
- Smart usability features: Includes auto fan speeds, adjustable louvers, self-diagnostics, and drain pump integration, improving installation flexibility and long-term maintenance ease.
Q&A
Q1: What is the cooling and heating capacity of this system?
A: It delivers approximately 10.5 kW cooling and 10.7 kW heating, suitable for medium to large residential rooms or light commercial spaces.
Q2: What type of air conditioner is it?
A: It is a 4-way cassette split system, with the indoor unit (CRE-100AS) mounted in the ceiling and the outdoor unit (URC-100AS) handling heat exchange.
Q3: How efficient is the system?
A: It uses an inverter twin-rotary compressor, offering efficient performance with COP around 3.7 (heating) and strong energy control for variable load conditions.
Q4: What size space is it suitable for?
A: Typically suited for large bedrooms, offices, shops, or open-plan areas around 40–65 m² (or larger depending on insulation and climate).
Q5: Does it support even air distribution?
A: Yes, it features 360° airflow with independent louvre control, ensuring even cooling or heating across the room.
Q6: Is it energy efficient for long-term use?
A: Yes, it includes MEPS compliance and inverter technology, helping reduce power consumption by adjusting output based on demand.
Maintenance Tips
- Clean air filters monthly (essential): Prevent airflow restriction, reduce energy use, and maintain strong 10.5 kW cooling / 10.7 kW heating performance.
- Professional coil cleaning annually: Indoor cassette and outdoor condenser coils must be kept clean to preserve efficiency and avoid compressor strain.
- Check condensate drain & pump: Ensure the built-in drain pump flows freely to prevent water leaks or ceiling overflow.
- Inspect 4-way airflow system: Keep louvers and discharge vents clear for balanced 360° air distribution and consistent room comfort.
- Outdoor unit clearance check: Remove dust, leaves, and debris around URC-100AS to maintain heat exchange efficiency and airflow.
- Verify refrigerant performance (technician-only): Ensure R410A system pressure is stable—low charge reduces cooling/heating capacity.
- Electrical connection inspection: Tighten terminals and check circuit breaker (typically 25A) for safe operation and reliability.
- Seasonal system test: Run cooling and heating modes before peak seasons to catch early faults in sensors or compressors.
- Use licensed HVAC servicing only: Internal work involves pressurized refrigerant and must be handled by qualified technicians.